Hydrostatic level sensors (also referred to as submersible pressure transmitter) are very often installed in outdoor applications, primarily in the water and wastewater industries, where open bodies of water, deep wells or boreholes are monitored. An excellent connection to ground is vital when installing hydrostatic level sensors, since no grounding or poor grounding can result in destruction or harm to the level sensor.
Common failures from improper grounding
Hydrostatic level sensors in outdoor applications are connected via cables to the PLC or routed to local telemetric systems. These cables can become an antenna, conducting electromagnetic or aerial voltage spikes down the wires to the sensor, causing an overload in the electronics and thereby premature failure. The media that’s measured may itself store energy such as a capacitor. This is due to lightning strikes, electrical surges or just static electricity. If you have not just a sufficiently low impedance ground connection for the level sensor, this may cause voltage surges that flash through the electronics causing them to overload and burn up.
Even if Bravery is too low to cause an overload of the electronics, it could cause electrolytic action due to the difference in voltage potential. Agitated causes the metal housing material of the hydrostatic level sensor to be ?eaten away? over long-term operation. Electrolytic corrosion pits will form in the material that may cause the diaphragm or housing to perforate, ultimately causing premature failure of the particular level sensor. This may be mistaken for chemical corrosion but is, actually, caused by the difference in voltage potential between the sensor and the encompassing liquid. With out a good ground the sensor becomes a sacrificial anode and is inevitably eaten away.
How to properly ground and protect a hydrostatic level sensor
WIKA level sensors can be found with optionally integrated lightning protection that acts on dangerous differences in the voltage potential between electronics, cabling and transmitter body, and routes any harmful voltages to ground before they are able to damage the internal circuitry. However, if the grounding for the transducer is poor, it’ll still have nowhere else to go but in to the electronics or body of the sensor, causing a premature failure.
In the case of metallic and plastic tanks, any isolated metal parts should be connected to a common ground having an impedance of < 100 Ohms. In applications onboard ships, where, essentially metal tanks are always present, all the different ground potentials ought to be from the ship?s main ground point during docking. In lakes and reservoirs, a minimal impedance link with ground may be hard to attain, but will be really worth the effort since it saves the hydrostatic level sensor electronics from failure. On artificial constructions or rock sites, even long copper spikes driven into the ground may not give a low-enough impedance to ground, so earthing grids could be embedded in to the ground to achieve the right resistance to ground.
Grounding of hydrostatic level sensors is a basic requirement of the reliable operation of level sensors, especially in outdoor applications, where overvoltage spikes and surges due to lightning strikes may appear regularly. Failure to provide adequate grounding can result in the failure of the particular level sensor.
Check out the profiles of WIKAs submersible pressure transmitters LH-20 and LS-10.